TTC-6-MOV-C-48DC-UT-I 2906838 PHOENIX CONTACT Medium surge protection with integrated status indicator for a.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

TTC-6-MOV-C-48DC-UT-I 2906838 PHOENIX CONTACT Medium surge protection with integrated status indicator for a..

TTC-6-MOV-C-48DC-UT-I

2906838

PHOENIX_CONTACT

Medium surge protection with integrated status indicator for a signal wire with grounded reference potential.

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $31.75
Unit price: $31.75

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2906838
Packing unit1 pc
Catalog pagePage 150 (C-4-2019)
GTIN4055626136943
Weight per Piece (excluding packing)20.000 g
Custom tariff number85363010
Country of originDE (Germany)

Drawings



Diagram

Diagram

Dimensional drawing

Dimensional drawing



Circuit diagram

Circuit diagram

Back to top

Dimensions

Height92 mm
Width6.2 mm
Depth69.5 mm (incl. DIN rail 7.5 mm)
Back to top

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 %
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20 (with end cover)
Back to top

General

Housing materialPBT
Flammability rating according to UL 94V-0
Colortraffic grey A RAL 7042
Mounting typeDIN rail: 35 mm
TypeDIN rail module, one-piece
Direction of actionLine-Earth Ground
Back to top

Protective circuit

IEC test classificationC1
C2
C3
Nominal voltage UN48 V DC
Maximum continuous voltage UC60 V DC
42 V AC
Rated current10 A (60 °C)
Operating effective current ICat UC≤ 100 µA
Residual current IPE≤ 100 µA
Nominal discharge current In(8/20) µs (line-earth)2 kA
Voltage protection level Up(line-earth)≤ 200 V (C1 - 600 A)
≤ 220 V (C2 - 4 kV)
≤ 150 V (C3 - 25 A)
≤ 160 V (C3 - 35 A)
Response time tA(line-earth)≤ 25 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 200 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm systemtyp. 650 kHz
Capacity (line-earth)5 nF
Resistance per path≤ 100 mΩ
Surge protection fault messageoptical
Impulse durability (line-earth)C1 - 600 A
C2 - 2 kA
C3 - 35 A
Back to top

Connection data

Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Back to top

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013
Back to top

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 4.027140201
eCl@ss 4.127130801
eCl@ss 5.027130801
eCl@ss 5.127130801
eCl@ss 6.027130800
eCl@ss 7.027130807
eCl@ss 8.027130807
eCl@ss 9.027130807
Back to top

ETIM

ETIM 2.0EC000943
ETIM 3.0EC000943
ETIM 4.0EC000943
ETIM 5.0EC000943
ETIM 6.0EC000943
ETIM 7.0EC000943
Back to top

UNSPSC

UNSPSC 6.0130212010
UNSPSC 7.090139121610
UNSPSC 1139121610
UNSPSC 12.0139121610
UNSPSC 13.239121620
UNSPSC 18.039121620
UNSPSC 19.039121620
UNSPSC 20.039121620
UNSPSC 21.039121620
Back to top

Datasheet - PDF

Title: Size: Type:
PDF CATALOG PHOENIX PROTECTION EN.pdf 27 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.